Solway - Computer Room (13:03)
Shed Mains Status: On
Harvest Mains Status: On
Truck Shed Mains Status: Off
CAT Generator Status: Standby
Computer Room Fire Alarm: Clear
UPS Area Fire Alarm: Clear
Computer Room Door: Closed
UPS 1 Input Voltage: Good
UPS 2 Input Voltage: Good
Air Con Input Voltage: Good
Computer Room Temperature: 23.6
Outdoor Ambient Temperature: 14.7
Red Power Draw: 5,074
Red Total Usage: 0.0
White Power Draw: 9,028
White Total Usage: 0.0
Blue Power Draw: 9,668
Blue Total Usage: 0.0
Total Power Draw: 23,769
Red Voltage: 238
White Voltage: 237
Blue Voltage: 236
UPS 1 Input: 237
UPS 1 Output: 245
UPS 2 Input: 234
UPS 2 Output: 244
Switchboard Nano Backup Battery: 6.9
East Total Power: 1,388
West Total Power: 1,253
East Red Voltage: 238
East White Voltage: 234
East Blue Voltage: 233
West Red Voltage: 238
West White Voltage: 233
West Blue Voltage: 235